GMC(LS)series AC contactor is suitable for using in the circuits up to the rated voltage 660VAC 50Hz or 60Hz, rated current 9A to 125A, making and breaking and frequent starting, controls the AC motor. Combined with the auxiliary contact group, air delayer, machine interlocking device etc, it is combined into the delay contactor, mechanical interlocking contactor, drat-delta starter, with the thermal relay, it is combined into the electro magnetic starter. This product conforms to the requirement of IEC 60947 4 -1 & GB14048.4 standards . |
Contactor Application
Type | GMC-9 | GMC-12 | GMC-18 | GMC-22 | GMC-32 | GMC-40 | GMC-50 | GMC-65 | GMC-75 | GMC-85 | ||
AC3 duty | 9A | 12A | 18A | 22A | 32A | 40A | 50A | 65A | 75A | 85A | ||
AC1 duty | 20A | 20A | 25A | 32A | 50A | 60A | 80A | 100A | 110A | |||
AC3 duty | 200~ 240V | 2.5kW 11A | 3.5kW 13A | 4.5kW 18A | 5.5kW 22A | 7.5kW 32A | 11kW 40A | 15kW 55A | 18.5kW 65A | 22kW 75A | 25kW 85A | |
380~ 440V | 4kW 9A | 5.5kW 12A | 7.5kW 18A | 11kW 22A | 15kW 32A | 18.5kW 40A | 22kW 50A | 30kW 65A | 37kW 75A | 45kW 85A | ||
500~ 550V | 4kW 7A | 7.5kW 12A | 7.5kW 13A | 15kW 22A | 18.5kW 28A | 22kW 32A | 30kW 43A | 37kW 60A | 45kW 64A | 45kW 75A | ||
690V | 4kW 5A | 7.5kW 9A | 7.5kW 9A | 15kW 18A | 18.5kW 21A | 22kW 25A | 30kW 33A | 37kW 47A | 45kW 47A | 45kW 52A | ||
thermal current(Ith) | 20A | 25A | 30A | 32A | 45A | 50A | 70A | 80A | 90A | 100A | ||
AC motor | Single phase | 115V | 0.5HP | 0.5HP | 1HP | 2HP | 2HP | 3HP | 3HP | 5HP | 5HP | 7.5HP |
230V | 1HP | 2HP | 3HP | 3HP | 5HP | 5HP | 7.5HP | 10HP | 15HP | 15HP | ||
Three phase | 200V | 2HP | 3HP | 5HP | 7HP | 7.5HP | 10HP | 10HP | 15HP | 20HP | 25HP | |
230V | 3HP | 3HP | 5HP | 7.5HP | 10HP | 10HP | 15HP | 20HP | 25HP | 30HP | ||
460V | 2HP | 7.5HP | 10HP | 10HP | 20HP | 25HP | 30HP | 50HP | 50HP | |||
575V | 5HP | 10HP | 15HP | 15HP | 20HP | 25HP | 30HP | 40HP | 50HP | 50HP |